Motor control Warema type "MSE Piccolo ZL UP"

  • Direct control of a sun shading drive via the sun shading control center or a push-button on site.
  • Several motor control units can be combined into a group and operated together by one push-button.
  • Operating mode of the push-button: Time logic
  • ZL: Time logic causes the MSE to go into self-retaining mode after the push-button has been actuated for approx. 2 seconds. Pressing the push-button for a shorter time generates a reversing pulse (for slat products).
  • The supply voltage for the MSE is generated in an external power supply unit or in a standard external projectile control unit.

Commission:
Prices visible after login
5 In stock
: 24.12.2024 - 28.12.2024 (DE - int. shipments may differ)
Description

The Piccolo ZL motor control unit (MSE) is an electrical controlnical control unit for direct control of 230Vsun shading drives. The MSE has a time logic function,
which enables convenient operation of your
sun shading system. Thanks to its compact designmSE can be accommodated in a flush-mounted box. The drives are supplied
via the
230 V mains. The MSE is supplied with 24 VDC SELV via the control cable. The MSEs can be

  • via push-buttons on site
  • combined to form a group
  • or operated via a central control unit

Function of the MSE Piccolo ZL

Local operation
After pressing the local control element, the sun shading device moves in the corresponding direction and stops after 2 seconds. If the "up/down" button remains
remains pressed, the MSE goes into self-retaining mode. The button can then be released. The sun shading device moves up or down to the end position.
low. If the movement is to be stopped in the self-retaining position, the button opposite the movement command must be pressed briefly.

Central operation
Local operation is disabled for the duration of a central command; any existing self-retaining function is deleted.

NOTE:
If the drive does not reach the "high" or "low" limit switch within 3 minutes, the drive is automatically switched off, regardless of whether a local or central operation command was given.


Group formation via control line
Several MSEs can be switched as a group via the common control line and controlled centrally via a control element. See Fig. 4 (connection diagram).